Excalibur Commercial Cooling Tower Side Stream Filters Brochure

EXCALIBUR TWIN PARALLEL COOLING TOWER SIDE STREAM 1-MICRON FILTER SYSTEM FILTER SPECIFICATIONS MODEL TOTAL MEDIA (ft3) CONTROL VALVE TANK SIZE (in) FLOW RATE (GPM) CYCLE DURATION (Min) PUMP (HP) APPROX. SPACE REQUIRED (in) Shipping Weight (lbs) CONTINUOUS PEAK BACKWASH BACKWASH FAST RINSE L W H EWS FTW15AG9SS1 18.0 1.5" 24x72 25.2 31.4 94.2 10.0 8.0 1.5 99 26 85 1960 EWS FTW2MQCAG14SS1 28.0 2"QC 30x72 39.2 49.2 147.4 10.0 8.0 2.0 117 32 95 2975 EWS FTW2HAG21SS1 42.0 2"H 36x72 56.6 70.8 212.0 10.0 8.0 3.0 131 38 98 4190 EWS FTW3AG28SS1 56.0 3" 42x72 77.0 96.2 288.0 10.0 8.0 5.5 157 44 110 6300 EWS FTW3AG37SS1 74.0 3" 48x72 100.6 125.8 378.0 10.0 8.0 5.5 163 50 107 7,600 Advantages • Controller with built-in motor control package • Centrifugal pump with easy serviceability • Electronically controlled backwash and fast rinse regeneration cycles • Historical operating data • Accurate flow meter with totalizer • Separate source regeneration • Pressure gauge readings for regeneration separate source, untreated source, pump discharge and post filter • Blue powder coated carbon steel frame 1” to 3” square tubing • Pressure relief valve to control maximum water pressure • 1-micron filtration • 40 psi pressure boost from cooling tower water supply or greater * L arge tanks can be replaced with system controlled multiple small tanks to reduce the regeneration drain flow and to get continuous filtered water. Contact Excalibur for more information. * Booster pump required for separate source regeneration, if combined pressure available is less than 40 psi.